CSION® 3R Alarm System

Innovative Indoor/Outdoor Alarm System

csion 3r

This alarm system monitors liquid levels in lift pump chambers, sump pump basins, holding tanks, sewage, agricultural, and other water applications. The CSION® 3R indoor/outdoor alarm can serve as a high or low level alarm depending on the float switch model used. This easy to install alarm features an innovative, sleek 2-color molded enclosure which integrates the red LED translucent beacon. Optional yellow LED models available.

The alarm sounds and the upper housing half illuminates when a potentially threatening liquid level condition occurs. The audible alarm can be silenced by pressing the Test/Silence button, but the alarm light will remain on until the condition is remedied. Once the condition is cleared, the alarm will automatically reset. A green “Power On” light indicates power to the alarm panel.

csion 3r

Features

  • 2-color molded enclosure offers a distinct look; upper translucent half illuminates in alarm condition
  • Removable lower cover provides greater access for easier field wiring while the internal circuitry remains protected
  • Interlocking enclosure features unique sound chamber to amplify the horn, while helping prevent moisture from entering
  • External mounting tabs for easy installation
  • Enclosure meets Type 3R water-tight standards
  • Enclosure has indicator marks on bottom for easy placement of cord entry locations
  • Automatic alarm reset, horn silence switch, and alarm test switch
  • Alarm horn sounds at 82 decibels at 10 feet (3 meters)
  • Alarm system (when installed on separate circuit) operates even if pump circuit fails
  • Green power on indicator
  • Includes auxiliary alarm contacts for easy attachment of remote devices

Options:

When ordered with the alarm, the system is available with:

  • Alternate float switch models for high or low liquid level warning
  • Premounted terminal block so enclosure can also be used as a junction box for splicing pump, pump switch, and pump power; meets NEC standard for junction boxes
  • 6 foot (1.8 meter) power cord with 120 VAC plug and liquid tight connector
  • Available with red or yellow LED alarm indication

Specifications

VOLTAGE:

  • PRIMARY: 120 VAC, 50/60 Hz, 3.8 watts max. (alarm condition)
  • SECONDARY: 9 VDC

ALARM ENCLOSURE: 6.7 x 5.3 x 2.5 inch (17.02 x 13.46 x 6.35 cm), indoor-outdoor, weatherproof, thermoplastic meets Type 3R water-tight standard

ALARM HORN: 82 decibels at 10 feet (3 meters)

AUXILIARY ALARM CONTACTS: 240 VAC / 30 VDC, 1.5 amps max., 50/60 Hz (circuit not supervised)

PRE-MOUNTED TERMINAL BLOCK (OPTIONAL): 20 amps, 120/240 VAC

POWER CORD (OPTIONAL): 6 foot (1.8 meter) cord with 120 VAC plug and two RCC8 1/2 inch liquid-tight connectors

FLOAT SWITCH: Control Duty Narrow Angle control switch with mounting clamp

  • CABLE: 15 feet (4.57 meters), flexible 18 gauge, 2 conductor (UL) SJOW, water-resistant (CPE)
  • FLOAT: 2.74 inch diameter x 4.83 inch long (7 cm x 12.3 cm), high impact, corrosion resistant polypropylene housing for use in sewage and non-potable water up to 140°F (60°C)
  • MAXIMUM WATER DEPTH: 30 feet (9 meters), 13 PSI
  • ELECTRICAL: 5 amps, 125 VAC/250 VAC, 50/60 H

For models and specifications
call toll free: 1-800-363-5842 or

Contact us